Communication Protocol
Optional HART™ communications on the 0-20 mA analog current (FSK) - used for maintenance, configuration changes and asset management, available in mA source output wiring options. RS-485 Modbus compatible communication link that can be used in computer controlled installations
Ambient Temperature
Operating & Storage: -76 °F to +185 °F (-60 °C to +85 °C)
Enclosure Rating
Stainless Steel 316L with electro polish finish
Heavy duty copper free aluminum (less than 1%), polyurethane painted
Mounting
Stainless Steel 316L with electro polish finish
Dimensions
Flame Detector 4"x 4.6"x 6.18"(101.6 x 117 x 157 mm)
Weight
Flame Detector (stainless steel 316L) 6.3 lb (2.9 kg)
Flame Detector (aluminum) 2.8 lb (1.3 kg)
Tilt mount 2.5 lb (1.1 kg)
Certifications/Approvals
strong>ATEX and IECEx:
- Ex II 2 G D
- Ex db eb op is IIC T4 Gb
- Ex tb op is IIIC T110 °C Db
- (Ta -50°Cto+85°C) IP66/68
FM/FMC
- Class I, Division 1, Groups B, C, and D, T4A
- Class II, III, Division 1, Groups E, F, and G, T4A
- Class I, Division 2, Groups A, B, C, and D, T4
- Ta = -50°C to +85°C
- Type 6P, IP66/68 2 m for 45 minutes
CSA/US:
Class I, Division 1, Groups B, C, and D, T4
Class II, III, Division 1, Groups E, F, and G, T4
Class I, Division 2, Groups A, B, C, and D, T4
Ta = -50 °C to +85 °C
Type 6P; IP 66/68 2 m for 45 minutes
TR CU (EAC):
- 1 Ex db eb op is IIC T4 Gb X
- Ex tb op is IIIC T110°C Db X
- (–55°C Ta +85°C)
Performance:
Reliability:
- Designed to meet IEC 61508 - SIL 3 (TÜV)
Marine: